Technical Parameters
| Technical parameter | Parameter value | 
| Brand | KLHA | 
| Temperature measuring range | -30℃~85℃ | 
| Temperature measuring accuracy | ±0.5℃ @25℃ | 
| Humidity measuring range | 0~100%RH | 
| Humidity accuracy | ±3%RH @25℃ | 
| Illuminance measuring range | 0~65535Lux | 
| Illuminance allow deviation | ±7% | 
| Repeatability test | ±5% | 
| Illuminance detection chip | Import digital | 
| Wavelength range | 380nm~730nm | 
| Communication Interface | RS485 | 
| Default baud rate | 9600 8 n 1 | 
| Power | DC9~24V 1A | 
| Running temperature | -30~85℃ | 
| Working humidity | 5%RH~90%RH | 
Product Size
 Wiring instructions
Why choose this product?
How to use?
Application solution
Pictures
Communication Protocol
    The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 . 
 
 1. Read data (function code 0x03) 
    Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 03 05 CB . 
| Address |  Function Code |  Start Address |  Data Length |  Check Code | 
| 01 | 03 | 00 00 | 00 03 | 05 CB | 
    For the correct query frame, the device will respond with data: 01 03 06 00 7B 00 00 00 00 C5 7F , response format:  
| Address |  Function Code |  Length | Data 1 | Data 2 | Data 3 | Check Code | 
| 01 | 03  | 06 | 00 79 | 00 7A | 00 7B |  C5 7F | 
    Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value as 121, assuming the data magnification is 100, then the real value is 121/100=1.21, Others and so on. 
 
 2. Common data address table 
| Configuration Address |  Register Address |  Register Description |  Data Type |  Value Range | 
| 40001 | 00 00 | temperature | Read Only | 0~65535 | 
| 40002 | 00 01 | humidity | Read Only | 0~65535 | 
| 40003 | 00 02 | Illuminance | Read Only | 0~65535 | 
| 40101 | 00 64 | Model Code | Read/Write | 0~65535 | 
| 40102 | 00 65 |  total number of measuring points |  read/write |  1~20 | 
| 40103 | 00 66 | device address | read/write | 1~249 | 
| 40104 | 00 67 | baud rate | read/write | 0~6 | 
| 40105 | 00 68 | communication mode | read/write | 1~4 | 
| 40106 | 00 69 | protocol type | read/write | 1~10 |